POWERFLEX® RV-K
Price is per 10 meter
APPLICATION
Powerflex® RV-K cable is suitable for all types of low voltage industrial-type connections, in urban grids, building installations, etc. Its high flexibility makes the installation process substantially easier and, as a result, is particularly suitable for use in difficult layouts. It can be buried or installed in a tube as well as outdoors without requiring additional protection. This cable can withstand damp conditions including total immersion in water (AD7).
CONSTRUCTION
Conductor
Electrolytic annealed copper conductor, class 5 (flexible) according to EN 60228 and IEC 60228. Insulation Cross-linked polyethylene insulation type DIX-3 according to HD 603-1 and type XLPE according to IEC 60502-1. The standard identification of insulated conductors according to HD 308 and UNE-21089-1, is the following:
1x Natural
2x Blue + Brown
3G Blue + Brown + Green/Yellow
3x Brown + Black + Grey
3x+1x Brown+Black+ Grey+ Blue (reduced cross-section)
4G Brown +Black+Grey + Green/Yellow
4x Brown+Black+ Grey+Blue
5G Brown + Black + Grey+Blue+ Green/Yellow
6 or more Black numbered + Green/Yellow
Outer sheath
Flexible PVC outer sheath, type DMV-18 according to HD 603-1 and type ST2 according to IEC 60502-1. Black colour.
CHARACTERISTICS
Electrical performance
Low voltage: 0,6/1 kV.
Thermal performance
Maximum service temperature: 90°C.
Maximum short-circuit temperature: 250°C (max. 5 s).
Minimum service temperature: -40°C (fixed and protected installations).
Minimum installation and handling temperature: 0°C (on cable surface).
Fire performance
Flame non-propagation according to EN 60332-1/IEC 60332-1.
Reaction to fire CPR: Eca according to EN 50575.
Reduced halogen emission. Chlorine <15%.
Environmental performance
Chemical & Oil resistance: Good.
UV Resistant according to UNE 211605.
Water resistance: AD7 immersion.
Mechanical performance
Minimum bending radius: 5x cable diameter.
Impact resistance: AG2 Medium severity.
Installation conditions Open Air. Buried. In conduit. In tray.
STANDARDS/COMPLIANCE
Accoring to
IEC 60502-1/UNE 21123-2
Standards and approvals
AENOR/BUREAU VERITAS/KEMA-KEUR/ROHS/CE
CPR (Construction Products Regulation)
Eca