TOPDRIVE® VFD (EMC) ROZ1-K (AS) 0,6/1 kV
Price is per meter
APPLICATION
TOPDRIVE® VFD (EMC) ROZ1-K (AS) cable has been specially designed for Variable Frequency Drive Motors and installations where it is necessary to limit the effects of electromagnetic interference (EMI). This is a flexible cable for fixed installations, for variable speed motors or pumps.
CONSTRUCTION
Conductor
Electrolytic annealed copper conductor, class 5 (flexible), according to EN 60228 and IEC 60228.
Protective Conductor
The ground conductor is divided into three conductors; the equivalent cross- section is approximately 50% of the section of the phase conductor. For 4G cables, ground conductor has the same cross-section as the phase conductors.
Insulation
Cross-linked polyethylene type XLPE according to IEC 60502-1, type HF XLPE 900C according to IEC 60092-360.
The standard identification of insulated conductors is the following:
3x+3G Grey+Brown+Black+Green/Yellow (3G) (from 6 mm2 onwards)
4G Grey + Brown + Black + Green/Yellow (up to 4 mm2)
Assembly of cores
For 3x+3G cables, the three phase conductors are cabled helically with the three protective conductors distributed in the interstices. For 4G cables, the three phase conductors and protection conductor are cabled helically.
Screen
Aluminium-polyester tape screen helically placed over the insulated conductors. Over the tape there is a tinned copper braid screen. The tape and the braid act as a double screen to cut out all of the electromagnetic interference, with a minimum total section of 10% of the phase conductor, ensuring a total shielding coverage.
Outer sheath
Polyolefin LSHF outer sheath, type ST8 according to IEC 60502-1 and type SHFI according to IEC 60092-360. black colour. The ripcord allows you to tear the outer sheath without damaging the screen.
CHARACTERISTICS
Electrical performance
Low voltage: 0,6/1 kV
Thermal performance
Maximum service temperature: 90°C.
Maximum short-circuit temperature: 250°C (max. 5 s).
Minimum service temperature: -40°C (fixed and protected installations)
Fire performance
Flame non-propagation according to EN 60332-1/IEC 60332-1.
Fire non-propagation according to EN 60332-3/ IEC 60332-3 and EN 50399.
Reaction to fire CPR: C-sla, dl, al according to EN 50575.
LSHF (Low Smoke Halogen Free) according to EN60754-1/IEC 60754-1
Low smoke emission according to EN 61034/IEC 61034: Light transmittance>80%.
Low corrosive gases emission according to EN 60754-2/IEC 60754-2.
Mechanical performance
Minimum bending radius: 10x cable diameter.
Impact resistance: AG2 Medium severity.
Environmental performance
Chemical & Oil resistance: acceptable.
UV Resistant according to EN 50618. Water resistance: AD5 Jets.
Installation conditions
Open Air.
Buried.
In conduit.
STANDARDS/COMPLIANCE
According to
IEC 60502-1/IEC 60092-353
Standards and approvals
BUREAU VERITAS/DNV-GL/ABS/
LLOYD'S REGISTER/ROHS/CE
CPR (Construction Products Regulation)
Cca-s1a, d1, a1