TOPFLEX® MS TRI-RATED / H07V2-K
Price is per meter
APPLICATION
Topflex® MS Tri-rated H07V2-K cable has been designed for the internal wiring of electrical cabinets, switch boards and small electrical devices. Due to its manufacturing characteristics, it can be used in conduit or in flexible motor ducts, transformers and other machinery in general. Industrial use. Electrical panel wiring.
CONSTRUCTION
Conductor
Electrolytic annealed copper conductor, class 5 (flexible), according to EN 60228, IEC 60228 and BS 6360.
Insulation
Flexible PVC, extra sliding, high service temperature type T13 according to EN 50363-3, and Class 43 UL 1581.
The special characteristics of the material ensure good easy-slide properties to the cable. The standard identification of insulated conductors is the following:
Blue RAL 5012
Brown RAL 8003
Black RAL 9005
Red RAL 3000
Green/Yellow RAL 6018/1021
Grey RAL 7000 Dark
Blue RAL 5010
White RAL 9010
Orange RAL 2003
Violet RAL 4005
Pink RAL 3015
CHARACTERISTICS
Electrical performance
Low voltage H05V2-K 300/500 V.
- H07V2-K 450/750 V BS 600/1000 V.
- UL 600V.
- CSA 600V
Thermal performance
Maximum service temperature: 90°C s/HD and BS, 105°C s / UL and CSA.
Maximum short-circuit temperature: 160°C (max 5 s).
Minimum service temperature: -40°C (fixed and protected installations).
Fire performance
Flame non-propagation according to EN 60332-1/IEC 60332-1.
VW-1 and FT2 according to UL 2556
Reaction to fire CPR: Eca according to EN 50575.
Mechanical performance
Minimum bending radius: 5x cable diameter.
Environmental performance
Chemical & Oil resistance: Acceptable.
Water resistance: AD3 Sprays. 0,50-6 mm2 10-16 mm2 25 mm2 onwards
STANDARDS/COMPLIANCE
According to
EN 50525-2-31/UL 758/CSA C22.2/BS 6231.
Standards and approvals
HAR/AENOR / UL LISTED/ROHS/CE.
CPR (Construction Products Regulation)
Eca