TOXFREE® XTREM ZH H07ZZ-F (AS)

TOXFREE® XTREM ZH H07ZZ-F (AS)

₱4,470.00
Skip to product information
TOXFREE® XTREM ZH H07ZZ-F (AS)

TOXFREE® XTREM ZH H07ZZ-F (AS)

₱4,470.00

Price is per meter

APPLICATION
Toxfree® Xtrem ZH H07ZZ-F (AS) is a flexible cable for mobile service, suitable for installations where low smoke and halogen free fumes under fire conditions are required. Suitable for installations where the cable must withstand medium mechanical stress, for machines in industrial and agricultural workshops, for motors and transportable machines on construction sites, for windmills and for agricultural applications.
   • Industrial use.
   • Mobile use.
   • Windmills.

CONSTRUCTION
Conductor
Electrolytic annealed copper conductor class 5 (flexible) according to EN 60228 and IEC 60228. Insulation Halogen free thermosetting rubber insulation, type E18 according to EN 50363-5. The standard identification according to HD 308, is the following:
1x                        Natural
2x                        Blue + Brown
3G                       Blue + Brown + Green/Yellow
4G                       Brown +Black+Grey+ Green/Yellow
5G                       Brown+Black+Grey+Blue+ Green/Yellow
6 or more            Black numbered + Green/Yellow

Outer sheath
Halogen free thermosetting flexible rubber outer sheath type EMB according to EN 50363-6. Black colour.

CHARACTERISTICS
Electrical performance
Low voltage 450/750 V.

Thermal performance
Maximum service temperature: 90°C.
Maximum short-circuit temperature: 250°C (max. 5 s).  
Minimum service temperature: -40°C (fixed and protected installations).

Fire performance
Flame non-propagation according to EN 60332-1/IEC 60332-1.  
Fire non-propagation according to EN 60332-3/IEC 60332-3.  
Reaction to fire CPR: B2-slb, dl,al, according to EN 50575 (see cross-section).
Low smoke emission according to EN 61034/IEC 61034: Light transmittance> 60%.
Low corrosive gases emission according to UNE-EN 60754-2/IEC 60754-2.

Mechanical performance
Minimum bending radius: 3x cable diameter < 12 mm.
                                          4x cable diameter z 12 mm. Impact resistance: AG2 Medium severity.

Environmental performance
Chemical & Oil resistance: excellent.
Grease & mineral oils resistance: excellent.
Water resistance:AD7 immersion.

Installation conditions
Open Air. In conduit.

Other
Meter by meter marking.

STANDARDS/COMPLIANCE
According to
EN 50525-3-21

Standards and approvals
HAR/AENOR/CE

CPR (Construction Products Regulation)
B2ca-s1b, d1,a1. (according to cross-section)