TOXFREE® ZH Z1C4Z1-K (AS)

TOXFREE® ZH Z1C4Z1-K (AS)

₱4,150.00
Skip to product information
TOXFREE® ZH Z1C4Z1-K (AS)

TOXFREE® ZH Z1C4Z1-K (AS)

₱4,150.00

Price is per meter

APPLICATION
Toxfree® Z1C4Z1-K is a screened LSHF safety cable. In case of fire, it does not emit toxic or corrosive gases, thereby protecting public health and avoiding any possible damage to electronic equipment.

For this reason, its use is highly recommended for public places and for all installations where it is necessary avoid to electric interference of nearby circuits.

CONSTRUCTION
Conductor
Electrolytic annealed copper conductor, class 5 (flexible) according to EN 60228 and IEC 60228.

Insulation
Special polyolefin insulation, with low smoke and halogen free fumes under fire conditions.
The standard identification of insulated conductors according to UNE 21089- 1 and HD 308 is the following:
1x                 Natural
2x                 Blue + Brown
3G                Blue + Brown + Green/Yellow
4G                Brown + Black + Grey + Green/Yellow
4x                 Brown+Black+Grey+Blue
5G                Brown + Black + Grey + Green/Yellow + Blue
6 or more    Black numbered + Green/yellow

Screen
Coverage of 100% composed by aluminium-polyester tape and tinned copper braid.

Outer sheath
Low Smoke Halogen Free (LSHF) polyolefin. Green colour, non-toxic and fire retardant.
The ripcord allows you to gently tear the outer sheath allowing you to gently peel it away without damaging the screen. Other outer sheath colours available on request.

CHARACTERISTICS
Electrical performance
Low voltage: 0,6/1 kV

Thermal performance
Maximum service temperature: 70°C.
Maximum short-circuit temperature: 160°C (max. 5 s).
Minimum service temperature: -40°C (static, with protection).

Fire performance
Flame non-propagation according to EN 60332-1/IEC 60332-1.
Fire non-propagation according to EN 60332-3/IEC 60332-3 and EN 50399.
Reaction to fire CPR: C-sla,dl, al according to 50575.
LSHF (Low Smoke Halogen Free) according to EN 60754-1/IEC 60754-1.
Low smoke emission according to EN 61034/IEC 61034: Light transmittance>80%.
Low corrosive gases emission according to EN 60754-2/IEC 60754-2.

Mechanical performance
Minimum bending radius: 5x cable diameter.
Impact resistance: AG2 Medium severity.

Environmental performance
Chemical & Oil resistance: acceptable.
UV Resistant according to EN 50618. Water resistance: AD5 Jets.

Installation conditions
Open Air.
Buried.
In conduit.

STANDARDS/COMPLIANCE
Based to
IEC 60502-1/UNE 21123-4

Standards and approvals
RoHS/CE

CPR (Construction Products Regulation)
Cca-s1a, d1, a1